Testo 570-2 set digital manifold for all measurement tasks on refrigeration systems and heat pumps, 4-way-valve block, internal data memory, integrated vacuum measurement, 3 temperature probe connections, calibration protocol, 2x clamp probes, software with USB cable, transport case, mains unit and batteries included. Record up to 999h measurement values. Refrigerant update by customer possible (via software EasyKool) Direct printout on site with optional Testo fast printer
Includes Testo 570 digital manifold, case, 2 x clamp probe, downloadable software, USB cable, mains unit, batteries and calibration protocol
Operating temperature -20øC to 50øC
Storage temperature -20øC to 60øC
Display - LCD
Life - > 40 h (wthout illumination)
Dimensions - 280 x 135 x 75 mm
Weight approx. - 1200g (without batteries)
Pressure media - HCFC, CFC, N, CO2, H2O
Pressure:
Low pressure - 50/50 bar (rel)
High pressure -
Overload - LP/HP: 52 bar
Accuracy - (at 22 øC) 0.5% fs (ñ1 digit)
Resolution - 0.01 bar / 0.1 psi
Connections - 3 x 7/16? UNF + 1 x 5/8? UNF
Temperature:
Measuring range - 50 to +150øC
Accuracy - (at 22 øC) ñ0.5øC (ñ 1 digit)
Resolution - 0.1 øC/0.1 øF
Probe connections - 3 x plug-in (NTC)
Meas. range (rel.):
Measuring range -1 bar to 0 bar
Resolution - 1mbar/ 1hPa/ 0.5Torr/ 0.5.5inH2O/ 100Pa/ 500Micron
Accuracy - (at 22 øC) 1 % fs
Refrigerants in instrument:
R12, R22, R123, R134a, R227, R290, R401A, R401B,
R402A, R402B, R404A,R406A, R407A, R407C, R408A,
R409A,R410A, R411A, R413A,R414B, R416A,R417A,
R420A, R421A, R421B, R422A,R422B, R422D, R424A,
R427A, R434A,R437A, R438A, R502, R503,
R507,R600, R600a, R718 (H2O), R744 (only in the
permitted range up to 40 bar), R1234yf